MECHANICAL UNIT 1
Model: Trane Intellipak SEHFC755
Gross cooling capacity: 75 Tons
Supply fan: 13 680 l/s (29 000 cfm)
External static pressure: 372 Pa (1.5")
Electrical supply (voltage/cycle/phase): 600 / 60 / 3
Heating module: 250 kW
Cooling module: 265 kW
Budget price: 72 000 $CAN (30 May 2006)

SPACES SERVED
level 0 — all spaces: toilets, circulation, storage, sprinkler room
level 1 — hall, ticket office, cloakroom, caterer, storage, toilets, foyer, circulation, orchestra
level 2 — balcony 1, circulation, storage
level 3 — balcony 2, circulation, storage, toilets, mechanical room
level 4 — catwalks (auditorium side), dimmer room

NOTE
Foyer and auditorium are not served at 100% simultaneously.
Mechanical dampers, controlled by thermostats, adjust ventilation requirements and distribution according to space occupation.

100 %100 %   200 %200 %   100 %100 %   200 %200 %